National Time fire alarm pull stations — 2016 recall

CPSC recalled about 3,500 National Time fire alarm pull stations in 2016 because the pull handle could break during activation.

Reviewed by Eric Aubrey · CT E-1 · NICET Fire Alarm Systems Level III

Known issue

The CPSC notice says the pull handle could break when a user attempted to activate the station, potentially preventing the fire alarm system from sounding.

Why technicians should know it

Legacy manual stations can remain installed long after a recall was announced. A technician who encounters an older National Time station should compare its identifying information with the official CPSC recall before making a determination.

Field check

Record the manufacturer, model, and identifying label information. Do not rely only on the faceplate appearance.

How to identify the station

Use the product label and model information, not just the pull-station shape or color. Photograph or record the manufacturer name, model number, and any date or serial information available. Compare those details directly with the CPSC notice because similar-looking National Time stations may not fall within the recalled population.

What to document in the service record

Replacement and retest

If the station matches the recalled product, follow the remedy in the official CPSC/manufacturer information and the site's approved impairment process. After corrective work, verify that operation produces the intended alarm at the control unit and that the required building response occurs before the system is returned to normal service.

Field takeaway

Identify the exact model, firmware, and date information before deciding the equipment is affected. Document what you find and follow the official source and your company's approved impairment/replacement process.

Official source

Always verify the current manufacturer or government notice before acting.